The ASAHI ESDA switchgear, for MV side which is designed in conformed arrangement and configuration in order to suit any specific application, form of metal enclosed & metal clad tinned copper busbar are provided for the phases and Neutral*, suited to the transformer primary voltage from 6.6 kV up to 24 kV, up to 35 kA type test design. The circuit-breaker switchgear type ASAHI ESDA is a factory assembled, type-tested switchgear for indoor installation according to IEC 62271-200. Loss of service continuity category: LSC 2B. Partition class: PM. Internal arc classification: IAC A FLR, Isc w 40 kA, arc duration: 1 s. Maximum ratings 12 kV / 3000 A / 40 kA and 24 kV / 2000A / 25 kA.
Rated voltage: (7.2/12/24) kV
Internal arc withstand current: (20/25/31.5/40/50) kA
Main busbar rated current: (630/1250/2000/2500/3150) A
Branch connection rated current: (630/1250/2000/2500/3150) A
Color of external surface: (RAL 7032/RAL 7035)
Rated voltage: (7.2/12/24) kV
Internal arc withstand current: (20/25/31.5/40/50) kA
Main busbar rated current: (630/1250/2000/2500/3150) A
Branch connection rated current: (630/1250/2000/2500/3150) A
Color of external surface: (RAL 7032/RAL 7035)
Rated voltage: (7.2/12/24) kV
Internal arc withstand current: (20/25/31.5/40/50) kA
Main busbar rated current: (630/1250/2000/2500/3150) A
Branch connection rated current: (630/1250/2000/2500/3150) A
Color of external surface: (RAL 7032/RAL 7035)